Salicru SPS 16 ATS manual

Salicru SPS 16 ATS
7.5 · 1
PDF manual
 · 16 pages
English
manualSalicru SPS 16 ATS
15

8. ANNEXES.

8.1. general TeChniCal sPeCiFiCaTions.

ELECTRICAL
INPUT SPS 16 ATS SPS 32 ATS
Rated voltage 200, 208, 220, 230, 240 V (see the rated factory value on the nameplate of the ATS).
Operating range 150.. 300 V AC.
Acceptable input voltage range ±5, 10, 15, 20 % (factory set at ± 15%).
Rated current 16 A. 32 A.
Rated frequency 50 or 60 Hz (see the rated factory value on the nameplate of the ATS).
Input frequency range ±5, 10, 15, 20 % (factory set at ± 10 %).
OUTPUT
Voltage Same as input.
Frequency Same as input.
Current 16 A. 32 A.
Overload protection Yes. Through electronic circuit. Yes. Through electronic circuit.
Transfer time 8..12 ms.
Performance 99 %.
Overload capacity > 111.. 125 % 60 s. (Protection through electronics).
Overload capacity > 125.. 150 % 30 s. (Protection through electronics)
Overload capacity > 150.. 200 % 5 s. (Protection through electronics)
Overload capacity > 200 % 1 s. (Protection through electronics)
Short circuit Protection through electronics.
ENVIRONMENTAL
Operating temperature 0.. 40 ºC.
Storage temperature -25.. 65 ºC permanent.
Operating humidity Up to 95% non-condensing.
Operating altitude 2,400 masl
Audible noise That of the sound alarm itself when activated.
Ventilation Natural.
Protection rating IP 20
CONNECTIONS
Input Connectors: 2 x IEC 60320 C20. Terminals: 2 groups of 3 (phase, neutral and earth).
Output Connectors: 1 x IEC 60320 C19 + 8 x IEC 60320 C13 Connectors: 2 x IEC 60320 C19 + 16 x IEC 60320 C13
COMMUNICATIONS
Interface RS232, USB and interface to relays (5 voltage-free contacts).
Slot for SNMP Yes.
INDICATORS
LCD + LEDs Input A, Input B, Overload, Alarm, Alarm mute.
Values shown on LCD display Input A and B: voltage and frequency. Output: voltage, frequency, current and % of load. Error code.
Monitoring software Free download from our website.
PHYSICAL
Dimensions (mm) -Depth x Width x Height- 285 x 440 x 44 (1 u). 295 (with terminal cover 370) x 440 x 88 (2 u).
Weight (kg) 4 6
STANDARDS
Safety EN-IEC 60950-1.
Electromagnetic compatibility (EMC) EN-IEC 62310-2.
Marking CE.
Quality and environmental management ISO 9001 and ISO 14001 (certified by SGS).

Tab. 8. General technical specifications.

SPS ATS AUTOMATIC TRANSFER SYSTEMUSER MANUAL

View the manual for the Salicru SPS 16 ATS here, for free. This manual comes under the category Not categorized and has been rated by 1 people with an average of a 7.5. This manual is available in the following languages: English. Do you have a question about the Salicru SPS 16 ATS or do you need help? Ask your question here

Need help?

Do you have a question about the Salicru and the answer is not in the manual? Ask your question here. Provide a clear and comprehensive description of the problem and your question. The better your problem and question is described, the easier it is for other Salicru owners to provide you with a good answer.

Number of questions: 0

General
Salicru
SPS 16 ATS | 658CB000001
Not categorized
8436035921911
English
User manual (PDF)
Power
Input operation voltage (min)150 V
Input operation voltage (max)300 V
AC input frequency50 - 60 Hz
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Output current16 A
Performance
Efficiency99 %
LED indicators
Design
Form factorRackmount
Rack capacity1U
Product colourBlack, Grey
DisplayLCD
SafetyIEC-60950-1
CertificationEN-55022; EN-55024, ISO 9001 & ISO 14001
Ports & interfaces
AC inlet type2 x C20 coupler
AC outlets quantity9 AC outlet(s)
AC outlet typesC13 coupler, C19 coupler
USB port
RS-232 ports2
SmartSlot
Operational conditions
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight & dimensions
Width438 mm
Depth275 mm
Height44 mm
Weight4000 g
show more

Can't find the answer to your question in the manual? You may find the answer to your question in the FAQs about the Salicru SPS 16 ATS below.

Is your question not listed? Ask your question here

No results