12 SALICRU

6. OPERATION.

This document is described and illustrated

considering that the power source of Input A is the

first that powers the device and that the voltage and

frequency parameters are within the acceptable range.

6.1. sTarTuP.

Make sure that all of the connections have been made

correctly, following the instructions on the labelling of the

device and in Chapter 5.

Make sure that all loads are ‘Off’.

Check that the power connection is correct.

Switch on the power sources connected to both inputs.

The SPS ATS will start up automatically after a second,

supplying voltage to the output sockets from the AC input.

For a short time, the LCD on the control panel will be

displayed as in Fig. 6, with the three LEDs (f), (g) and (h)

illuminated and, after this time, it will be displayed as in

Fig. 7 with LEDs (f) ‘INPUT A’ and (g) ‘INPUT B’ illuminated.

Fig. 6. Initial screen shown in the first moments of device

startup.

Fig. 7. Screen shown after the beginning of startup.

Start the loads, making sure that the rated supply of each

model is not exceeded.

6.2. ForCed manual TransFer oF inPuT.

Press and hold down key (b)
A/B

on the control panel for

at least two seconds until two short beeps are heard. The

illustration in Fig. 8 will be displayed on the screen.

To confirm the transfer, press key (b)

A/B

on the control

panel again for more than two seconds.

The system will switch the power supply of the load to

‘INPUT B’ provided that the voltage and/or frequency are

normal (within the predefined range) and it will be shown

on the screen as in Fig. 9.

If the voltage and/or frequency however is abnormal, it will

not allow the transfer and it will be shown on the screen

as in Fig. 10.

Fig. 8. Transfer confirmation request screen.

Fig. 9. Transfer to input B screen.

Fig. 10. Input B abnormal mains screen.

Fig. 7 and Fig. 9 show the voltage values by way of

example (220 V in the illustration).

6.3. reading The ParameTers.

Use key (c) to select the source of Input A, Input B or

Output whose readings you wish to display. Cyclically with

each press, it jumps to the next, showing a pointer below

the source in which it is located.

Use key (d)
i

to see the reading of the different

parameters on the screen, according to the source selected:

For Input A and B: Input voltage and frequency.

For output: Voltage, frequency, current and % of output

load.

6.4. audible alarm.

The device has an audible alarm that is activated in the

event of any of the faults or incidents shown in Tab. 4.

By pressing key (a) , it is possible to mute any alarm

that is activated, but only one by one, independently and

every time it occurs. It is not possible to mute the alarm

permanently.

View the manual for the Salicru SPS 16 ATS here, for free. This manual comes under the category Not categorized and has been rated by 1 people with an average of a 7.5. This manual is available in the following languages: English. Do you have a question about the Salicru SPS 16 ATS or do you need help? Ask your question here

Need help?

Do you have a question about the Salicru and the answer is not in the manual? Ask your question here. Provide a clear and comprehensive description of the problem and your question. The better your problem and question is described, the easier it is for other Salicru owners to provide you with a good answer.

Number of questions: 0

General
Salicru
SPS 16 ATS | 658CB000001
Not categorized
8436035921911
English
User manual (PDF)
Power
Input operation voltage (min)150 V
Input operation voltage (max)300 V
AC input frequency50 - 60 Hz
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Output current16 A
Performance
Efficiency99 %
LED indicators
Design
Form factorRackmount
Rack capacity1U
Product colourBlack, Grey
DisplayLCD
SafetyIEC-60950-1
CertificationEN-55022; EN-55024, ISO 9001 & ISO 14001
Ports & interfaces
AC inlet type2 x C20 coupler
AC outlets quantity9 AC outlet(s)
AC outlet typesC13 coupler, C19 coupler
USB port
RS-232 ports2
SmartSlot
Operational conditions
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight & dimensions
Width438 mm
Depth275 mm
Height44 mm
Weight4000 g