Proceed as follows (see Fig. 4):

Using the supplied screws, fix the two angles to the

side of each device, respecting its mounting orientation.

Fix the ATS to the frame of the rack cabinet using the

screws.

Optionally, guides to facilitate the mounting of the

ATS can be installed in the rack cabinet. Upon request,

we can supply the user with universal slides to use as

guides.

5.2.2.1. Preliminary considerations before connection and siting

requirements.

Check that the information on the device’s nameplate is

that required for installation.

Depending on the SPS ATS model, loads can be connected to:

Eight or sixteen IEC 60320 C13 connectors.

Plus one or two IEC 60320 C19 connectors.

Under no circumstances should all of the loads connected

to the sockets exceed 16 or 32 A respectively, according to

the model.

It is worth mentioning that the SPS 32 ATS has two 32 A

circuit breakers to enable the user to optionally connect all

of the loads to the same group of sockets. Independently,

the overload alarm will detect any excess load connected

to the output, since the detector performs a reading before

distribution.

The cross section of the input line cables will be determined

by the current indicated on the nameplate of each device,

in compliance with local and/or national Low-Voltage

Electrotechnical Regulations.

Regarding the output, although the total limit is the same,

the admissible current for each type of connector must be

considered:

For the IEC 60320 C13, it is 10 A.

And for the IEC 60320 C19, it is 16 A.

This product complies with the safety requirements to be

operated in locations with restricted access in accordance

with safety standard EN IEC 62310-1, which establishes

that the owner must ensure that:

The device can only be accessed by technical personnel or

users who have been properly trained on the restrictions

applicable to the location and the precautions that must

be followed.

Access to the device must be under lock and key or other

security measures and monitored by responsible personnel.

5.3. CONNECTIONS.

When powering one of the unit’s inputs with a UPS,

both with independent UPSs or even with an electric

power generator, the user should take the necessary

precautions against direct or indirect contact since these

devices are energy generators.

5.3.1. Connection of the input for SPS 16 ATS models.

As the device has Class I protection against electric

shock, it is obligatory and essential for the AC input

socket to have the earth conductor ( ) installed. Check

that this is the case before continuing.

Take one of the power cables supplied, insert the female

IEC connector into its equivalent on the SPS and the Schuko

plug on the other end of the cable into an AC power socket.

The cross section of the power socket cables must be

appropriate for the current of the device, in compliance

with local and/or national Low-Voltage Electrotechnical

Regulations.

Proceed in the same way for the other input, which will be

powered by a source that is different to the previous socket.

5.3.2. Connection of the input for SPS 32 ATS models.

As the device has Class I protection against electric

shock, it is obligatory and essential to connect the

earth conductor ( ) to each group of input terminals.

Check that this is the case before continuing.

The cross section of both input cables must be appropriate

for the current of the device, in compliance with local and/

or national Low-Voltage Electrotechnical Regulations.

Connect the input cables to one of the terminals in the

group, respecting the order of the phase and neutral

indicated on the labelling.

Proceed in the same way for the other input, which will

ideally be powered by a source that is different to the

previous one.

5.3.3. Connection of the loads to the output connectors.

Connect the loads to the IEC connectors respecting the

limitations of each model and type of connector:

For the IEC 60320 C13, it is 10 A.

And for the IEC 60320 C19, it is 16 A.

Check that all of the load connected to the output does not

exceed the rated current of the SPS according to the model:

5.3.4. Communication port.

5.3.4.1. RS232, USB and interface to relays port.

The communications line -COM- constitutes a very

low voltage safety circuit. To preserve the quality, it

must be installed separately from other lines carrying

dangerous voltages (power distribution line).

The RS232 and USB interfaces are useful for the monitoring

software and updating the firmware.

It is not possible to use both the RS232 and USB ports at

the same time.

The RS232 port consists of the transmission of serial data

in such a way that a large amount of information can be

sent through a 4-wire communication cable (see Tab. 1).

The USB port is compatible with the USB 1.1 protocol and the

signal arrangement of the connector is indicated in Tab. 2.

In addition to that corresponding to the RS232, another

DB9 connector is supplied for that of the interface to

relays which delivers the normally open (NO) contacts of

potential-free relays (see Tab. 3). The maximum voltage and

current applicable to these is 24 V DC and 1A.

View the manual for the Salicru SPS 16 ATS here, for free. This manual comes under the category Not categorized and has been rated by 1 people with an average of a 7.5. This manual is available in the following languages: English. Do you have a question about the Salicru SPS 16 ATS or do you need help? Ask your question here

Need help?

Do you have a question about the Salicru and the answer is not in the manual? Ask your question here. Provide a clear and comprehensive description of the problem and your question. The better your problem and question is described, the easier it is for other Salicru owners to provide you with a good answer.

Number of questions: 0

General
Salicru
SPS 16 ATS | 658CB000001
Not categorized
8436035921911
English
User manual (PDF)
Power
Input operation voltage (min)150 V
Input operation voltage (max)300 V
AC input frequency50 - 60 Hz
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Output current16 A
Performance
Efficiency99 %
LED indicators
Design
Form factorRackmount
Rack capacity1U
Product colourBlack, Grey
DisplayLCD
SafetyIEC-60950-1
CertificationEN-55022; EN-55024, ISO 9001 & ISO 14001
Ports & interfaces
AC inlet type2 x C20 coupler
AC outlets quantity9 AC outlet(s)
AC outlet typesC13 coupler, C19 coupler
USB port
RS-232 ports2
SmartSlot
Operational conditions
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight & dimensions
Width438 mm
Depth275 mm
Height44 mm
Weight4000 g
show more