- 10 -

MAINTENANCE

COMPRESSOR

The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should
provide years of satisfactory operating service.
Should the refrigerant charge be lost, recharging ports (access ttings) on the suction and discharge sides of the
compressor are provided for recharging and/or checking suction and discharge pressures.
Under no circumstances should the access tting covers be loosened, removed or tampered with.
Breaking of seals on compressor access ttings during warranty period will void warranty on hermetic system.
Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for
recharging the air conditioner.

INLET AIR FILTER

Proper maintenance of the inlet air lter, located behind the front cover, will assure normal operation of the air
conditioner. If lter maintenance is delayed or ignored, the maximum ambient temperatures under which the unit
is designed to operate will be decreased.
If the compressor’s operating temperature increases above designed conditions due to a dirty or clogged
lter (or plugged condenser coil), the air conditioner’s compressor will stop operating due to actuation of the
thermal overload cut-out switch located on the compressor housing. As soon as the compressor temperature
has dropped to within the switchs cut-in setting, the compressor will restart automatically. However, the above
condition will continue to take place until the lter or coil has been cleaned. It is recommended that power to
the air conditioner be interrupted intentionally when abnormally high compressor operating temperature causes
automatic shut-down of the unit. The above described shutdown is symptomatic of a clogged or dirty lter, thus
causing a reduction in cooling air ow across the surface of the compressor and condenser coil.
Do not run the air conditioner for extended periods of time with the lter removed. Particles of dust, lint, etc., can
plug the ns of the condenser coil which will give the same reaction as a plugged lter. The condenser coil is not
visible through the lter opening, so protect it with a lter.
Continued operation under the above conditions can and will damage and shorten compressor life. The air
conditioner is available with an easily removable inlet lter to facilitate necessary cleaning. There should be no
reason to neglect this necessary maintenance.

HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER

RP aluminum washable air lters are designed to provide excellent ltering eciency with a high dust holding
capacity and a minimum amount of resistance to air ow. Because they are constructed entirely of aluminum
they are lightweight and easy to service. Optimum lter performance is maintained by recoating the lters
after washing with RP Super Filter Coat adhesive. To achieve maximum performance from your air handling
equipment, air lters should be cleaned on a regular basis.
The inlet air lter is located behind the front cover. To access lter, pull ring protruding from slot in bottom of front
cover. The lter may now be cleaned or new lter installed.
Cleaning Instructions:
1. Flush the lter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.
2. After ushing, allow lter to drain. Placing it with a corner down will assure complete drainage.
3. Recoat the lters with RP Super Filter Coat adhesive. When spraying lter do so from both sides
for maximum concentration of adhesive.

Manual

View the manual for the Hoffman T150116G100 here, for free. This manual comes under the category air-conditioning and has been rated by 1 people with an average of a 7. This manual is available in the following languages: English. Do you have a question about the Hoffman T150116G100 or do you need help? Ask your question here

Need help?

Do you have a question about the Hoffman and is the answer not in the manual?

  • Receive updates on solutions
  • Get answers to your question

Question and answer

Number of questions: 0

Hoffman T150116G100 specifications

Below you will find the product specifications and the manual specifications of the Hoffman T150116G100.

The Hoffman T150116G100 air-conditioning unit is designed for industrial automation, telecommunications equipment, package handling equipment, security and defense systems, and more. It has a housing made of metal and a cooling capacity of 235 watts (nominal). The refrigerating medium used is R134A, with a weight of 113 grams. This air-conditioning unit is suitable for various applications where precise temperature control is required. The metal housing ensures durability and protection for the internal components. With a cooling capacity of 235 watts, it can effectively regulate the temperature in the specified area. The use of R134A refrigerant allows for efficient cooling performance. The Hoffman T150116G100 air-conditioning unit is a reliable option for maintaining temperature-sensitive equipment and systems. Its compact design makes it suitable for installation in different environments. The unit is designed to meet the cooling needs of various industries, making it a versatile choice for a range of applications. The use of quality materials ensures longevity and consistent performance.

General
BrandHoffman
ModelT150116G100 | T150116G100
Productair-conditioning
LanguageEnglish
FiletypeUser manual (PDF)
Technical details
Product colorGray
Housing materialMetal
Features
Product colorGray
Cooling capacity in watts (nominal)235 W
Refrigerating mediumR134A
Refrigerating medium weight113 g
Operating temperature (cooling) (T-T)-40 - 55 °C
Heating capacity in watts (nominal) (Average heating season)- W
Heating capacity in watts (nominal) (Colder heating season)- W
Heating capacity in watts (nominal) (Warmer heating season)- W
Seasonal efficiency rating (cooling) (SEER)-
Seasonal efficiency rating (heating) (SCOP) (Warmer heating season)-
Seasonal efficiency rating (heating) (SCOP) (Average heating season)-
Seasonal efficiency rating (heating) (SCOP)-
Seasonal efficiency rating (heating) (SCOP) (Colder heating season)-
Thermostat range- °C
TypeAir conditioner indoor unit
Multi-split-
Air conditioner functionsCooling
Inverter technology-
Ionizer-
Cooling capacity (min)800 BTU/h
Power
Energy efficiency class (cooling)-
Energy efficiency class (heating) (Warmer heating season)-
Energy efficiency class (heating) (Average heating season)-
Energy efficiency class (heating) (Colder heating season)-
AC input voltage100 - 115 V
AC input frequency50 - 60 Hz
Hourly energy consumption (cooling)- kWh
Hourly energy consumption (heating)- kWh
Annual energy consumption (heating) (Warmer heating season)- kWh
Annual energy consumption (cooling)- kWh
Annual energy consumption (heating) (Colder heating season)- kWh
Annual energy consumption (heating) (Average heating season)- kWh
Design load (cooling)- kW
Design load (heating) (Colder heating season)- kW
Design load (heating) (Warmer heating season)- kW
Design load (heating) (Average heating season)- kW
AC input voltage100 - 115 V
AC input frequency50 - 60 Hz
Design load (cooling)- kW
Design load (heating) (Colder heating season)- kW
Design load (heating) (Warmer heating season)- kW
Design load (heating) (Average heating season)- kW
Indoor unit
Indoor unit weight12000 g
Indoor unit width191 mm
Indoor unit depth160 mm
Indoor unit height400 mm
Indoor unit noise level (high speed)53 dB
Indoor unit weight12000 g
Indoor unit width191 mm
Indoor unit depth160 mm
Indoor unit height400 mm
Indoor unit noise level (high speed)53 dB
Certificates
CertificationUL/cUL Listed\nCE\nEAC
CertificationUL/cUL Listed\nCE\nEAC
Outdoor unit
Outdoor unit noise level- dB
Outdoor unit noise level- dB
Network
Wi-Fi-
Design
Product colorGray
TypeAir conditioner indoor unit
Multi-split-
Performance
Cooling capacity in watts (nominal)235 W
Refrigerating mediumR134A
Refrigerating medium weight113 g
Operating temperature (cooling) (T-T)-40 - 55 °C
Heating capacity in watts (nominal) (Average heating season)- W
Heating capacity in watts (nominal) (Colder heating season)- W
Heating capacity in watts (nominal) (Warmer heating season)- W
Seasonal efficiency rating (cooling) (SEER)-
Seasonal efficiency rating (heating) (SCOP) (Warmer heating season)-
Seasonal efficiency rating (heating) (SCOP) (Average heating season)-
Seasonal efficiency rating (heating) (SCOP)-
Seasonal efficiency rating (heating) (SCOP) (Colder heating season)-
Thermostat range- °C
Air conditioner functionsCooling
Cooling capacity (min)800 BTU/h
show more

Frequently Asked Questions

Can't find the answer to your question in the manual? You may find the answer to your question in the FAQs about the Hoffman T150116G100 below.

What certifications does the Hoffman T150116G100 have?

The Hoffman T150116G100 has the following certifications: UL/cUL Listed\nCE\nEAC.

What does BTU stand for?

BTU stands for British Thermal Unit and is a unit used to indicate cooling power.

What does R-410A stand for?

R-410A is a refrigerant used in machines that cool to zero degrees Celsius.

How often should I clean the filters of my Hoffman air conditioner?

The cleaner the filters, the better the air quality. This is why it is recommended to clean the filters of your Hoffman air conditioner at least four times a year.

What energy label does the Hoffman T150116G100 have?

The Hoffman T150116G100 has energy label -.

How do I properly install the air-conditioning unit?

To ensure proper installation, make sure you position the unit in a well-ventilated area, away from direct sunlight or heat sources. Use the provided brackets and screws for secure mounting on a stable surface such as a wall. Additionally, connect the unit to a proper electrical outlet using a dedicated circuit for optimal performance.

How can I control the temperature and fan speed of the air-conditioning unit?

The air-conditioning unit features a user-friendly control panel. To adjust the temperature, use the temperature control buttons to set the desired temperature. To regulate the fan speed, use the fan speed control buttons to switch between low, medium, and high settings.

How can I effectively clean the air filters of the unit?

Maintaining clean air filters is crucial for optimal performance. To clean the air filters, carefully remove them from the unit and rinse them with warm water or use a vacuum cleaner to remove any dust or debris. Allow the filters to dry completely before reassembling and reinstalling them.

How do I troubleshoot if the air-conditioning unit is not functioning properly?

If you encounter any issues, first ensure that the unit is receiving power. Check the power cord, outlet, and circuit breaker. If the unit is still not functioning, try resetting it by turning it off for a few minutes and then turning it back on. If the problem persists, consult a qualified technician for further assistance.

How can I maximize energy efficiency with the air-conditioning unit?

To optimize energy efficiency, consider utilizing the programmable temperature settings. Set the temperature at a comfortable level during occupied periods and slightly higher during unoccupied periods. Additionally, ensure the room is well-insulated by sealing any air leaks and closing curtains or blinds to prevent heat gain from sunlight. Regular maintenance, such as cleaning the filters and ensuring proper airflow, also contributes to energy efficiency.

What is the housing material of the Hoffman T150116G100 air-conditioning unit?

The housing material of the Hoffman T150116G100 is metal. This means it provides durability and protection for the internal components, making it a reliable choice for users.

What is the cooling capacity in watts of the Hoffman T150116G100?

The cooling capacity in watts of the Hoffman T150116G100 is 235 W. This indicates that it has a moderate cooling power, suitable for small to medium-sized rooms.

What refrigerating medium does the Hoffman T150116G100 use?

The Hoffman T150116G100 uses refrigerating medium R134A. This is a common and environmentally-friendly coolant, ensuring efficient cooling performance.

How high is the indoor unit of the Hoffman T150116G100?

The indoor unit height of the Hoffman T150116G100 is 400 mm. This compact size allows for easy installation in different spaces without taking up too much room.

What is the indoor unit noise level (high speed) of the Hoffman T150116G100?

The indoor unit noise level (high speed) of the Hoffman T150116G100 is 53 dB. This means it operates relatively quietly, providing a comfortable environment for users without causing disturbance.

Is the manual of the Hoffman T150116G100 available in English?

Yes, the manual of the Hoffman T150116G100 is available in English .