62 Mounting and installation work

5.7.6 Installation work external connections

Connecting the external safety chain
PEPESC2SC1NL1
MAIN SUPPLY
K2
J3
B3
B2
B1
Control compartment
Do not apply extraneous
voltage via K2!
DANGER: 230 V
The potential-free contacts of external moni t or ing devic-
es (e.g. ventilation interlock, safety high limit humidistat,
airow monitor, etc.) are connected in series (external
safety chain "K2") to the terminals "SC1" and "SC2" on
the driver board in accordance with the wiring diagram.
The connecting cable must be led through a cable gland
or grommet into the control compartment.
Caution! A high limit humidistat is highly recomen-
ded to prevent risk of over-humidication and potential
damage to property.
Note: If, for whatever reason, no external monitoring
devices are connected, a cable bridge "J3" must be
installed on the contacts "SC1" and "SC2" of the ter-
minal block.
CAUTION! Do not apply any extraneous voltage to
contacts "SC1" and "SC2" via the contacts of the
external monitoring devices.
Connecting the demand or humidity signal
CONT. SIGN.
GNDINV+
+
A1
Y
24V
10V
JP1
24V/
10V
Control compartment
The signal cable of an external controller or of a humidity
sensor (if the internal P/PI controller is used) is to be
connected according to the wiring diagram to the ter-
minals "IN" and GND" on the driver board in the control
compartment. The admissible signal values can be found
in the technical data table in the operation manual. The
connecting cable must be led through a cable gland or
grommet into the control compartment.
Note: if the external controller or the humidity sensor
shall be supplied with 10 V or 24 V from the driver board
(terminal “A+”), the jumper JP1 must be set to 10V or
24V accordingly.
Note: The admissible humidity control signal values
can be found in the technical data table in the operation
manual.
If a shielded signal cable is used, connect the cable
shield to terminal "GND".
Caution! If the signal cable shield is already connected
to a po ten tial or a grounded conductor, do not con-
nect it to terminal "GND".

Manual

View the manual for the Condair EL here, for free. This manual comes under the category humidifiers and has been rated by 1 people with an average of a 8.6. This manual is available in the following languages: English. Do you have a question about the Condair EL or do you need help? Ask your question here

Index

Need help?

Do you have a question about the Condair and is the answer not in the manual?

  • Receive updates on solutions
  • Get answers to your question

Question and answer

Number of questions: 0

Condair EL specifications

Below you will find the product specifications and the manual specifications of the Condair EL.

General
BrandCondair
ModelEL
Producthumidifier
LanguageEnglish
FiletypeUser manual (PDF)

Frequently Asked Questions

Can't find the answer to your question in the manual? You may find the answer to your question in the FAQs about the Condair EL below.

Is the manual of the Condair EL available in English?

Yes, the manual of the Condair EL is available in English .

Is your question not listed? Ask your question here

No results