57Mounting and installation work

L1 L2 L3
L1 L2 L3 PE
Q5
F5
200-600 V/3~/50..60 Hz
200-240 V/1~/50..60 Hz
L1 N PE
Q5
F5
L1 L2 L3
K1
X0
140Ω...10kΩ
A2
On/Off
A3
GND
IN
V+
IN
V+
B3
K2
B2
B1
L1 N PE
F6
Q6
230 V/1~/50..60 Hz
J3
230V/5A
A4
+ +
A1
JP1
24V 10V
JP1
24V 10V
J1
L1 N PE
M
L2 L3L1
L1 N PE
L1 L2 L3 PE
Q5
F5
L2 L3
L1
N PEL1
L1 L2 L3 N
Q5
F5
PE
PEPESC2SC1NL1
INLET SPARE/DRAIN
CONTA.
CONT. SIGN.
GNDINV+
24V
10V
CONT.INLET
L1FU
L1SW
N
MAIN SUPPLY
MODULE B
PEP1NP
LIM. SIGN.
GNDIN
SPARE DRAIN
SWITCH
L1SCNSW L1SCNSW L1SWNSW L1SW
F1 (1 AT)
COMM
HB OK
JP3
JP1
LEVEL
LOW 24V GND
CURRENT SENSOR
SC OK
HWS
BLOWER
IN24V
ON/OFF
IN24V
SPARE1SPARE2T1
D+GND
D-
GND24V
D+
GND D-
RS4852RS4851PWR IC
SW1
F3 (4 AT)
3V
CR2032
GND + GND + GND + 24V GND
BMSLinkupSABJ14
(USB)
(RJ45)
BAT
SD
J7
J4J8J11
ACCESSORY BOARD
REMOTE BOARD
F1 (100 mA)
H1
Error
1 2 3
Service
4 5 6
Steam
7 8
Unit On
9 10
H2
Hyg. Valve A FAN B
1 2 3
Hyg. Valve B
4 5 6
7 8
FAN A
9 10
Y Z
B4

Control compartment

5.7.2 Wiring diagram Condair EL 5...45 - Single units "S" and "M"

Fig. 26: Wiring diagram Condair EL 5...45 - Single units "S" and "M"

A1 Continuous humidity controller (active) or humidity sensor
A2 Ohmic humidity ontroller (passive), set jumper JP1 to 10V
A3 On/Off humidity controller, set jumper JP1 to 24V
A4 Limiter signal
B1 Ventilation interlock
B2 Airow monitor
B3 Safety humidistat (highly recommended)
B4 External enable contact
F1 Internal fuse driver board 24V supply (1 A, slow acting)
F3 Internal fuse driver board 230V supply (4 A, slow acting)
F5 External fuse heating voltage supply (see table in chapter 5.7.7)
F6 External fuse control voltage (max. 10 A, slow acting)
H1 Remote operating and fault indication (option)
H2 Accessory board (option) for the control of an external fan of the AHU as well
as the optional external valve for the water supply line ushing
J1 Jumper wire, if blower pack safety loop is not connected
J3 Jumper wire, if no monitoring devices are connected to SC1 and SC2
J4 Jumper for activating the termination resistor for Modbus or BACnet MSTP
network (Jumper must be connected, if the Condair EL is the rst or the last
unit in the network)
J7 Jumper for activating Modbus or BACnet MSTP communication via RS485
interface (J6). If jumper is not in place no communication will take place
through the RS485 interface.
K1 Mains contactor (heating voltage) unit A/unit B
K2 External safety circuit (230V/5A)
M Motor blower pack
Q5 External electrical isolator heating voltage supply
Q6 External electrical isolator control voltage supply
SW1 Rotary switch module identication (must be left on position "0" Module A)
X0 Terminal Heating voltage supply (option)
Control board
Driver board
Option TR (3Ph)
Option CVI (3Ph+N)
6.3 A, slow acting
6.3 A, slow acting
Ethernet (RJ45)
IP network / BMS BACnet IP
RS 485
BACnet MSTP

Manual

View the manual for the Condair EL here, for free. This manual comes under the category humidifiers and has been rated by 1 people with an average of a 8.6. This manual is available in the following languages: English. Do you have a question about the Condair EL or do you need help? Ask your question here

Index

Need help?

Do you have a question about the Condair and is the answer not in the manual?

  • Receive updates on solutions
  • Get answers to your question

Question and answer

Number of questions: 0

Condair EL specifications

Below you will find the product specifications and the manual specifications of the Condair EL.

General
BrandCondair
ModelEL
Producthumidifier
LanguageEnglish
FiletypeUser manual (PDF)

Frequently Asked Questions

Can't find the answer to your question in the manual? You may find the answer to your question in the FAQs about the Condair EL below.

Is the manual of the Condair EL available in English?

Yes, the manual of the Condair EL is available in English .

Is your question not listed? Ask your question here

No results