The water supply is to be carried out according to the gure found in chapter chapter 5.5.1 and the appli-
cable local regulations for water installations. The indicated connection specications must be observed.
– The installation of the lter valve (accessory "Z261", alternatively a shut-off valve and a 5 µm water
lter can be used) should be made as close as possible to the steam humidier.
Note: on large units with two steam cylinders, on double units and on Linkup systems each unit
must be connected separately via a lter valve (or shut-off valve and water lter) to the water supply.
– Admissible water supply pressure:
– 1.0…10.0 bar (units without drain water cooling)
– 2.0…10.0 bar (units with drain water cooling)
Note: the supply water system must be hammer-free. For mains pressures >10 bar, the connection
must be made via a pressure reducing valve (adjusted to 2.0 bar). For mains pressures <1.0 bar
(units without drain water cooling) <2.0 bar (units with drain water cooling) please contact your
Condair supplier.
– Notes on water quality:
– For the water supply of the Condair EL, use exclusively untreated drinking water.
– The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since these
additives may endanger health and affect proper operation.
– If the Condair EL is to be operated with softened or partly softened water, please contact your
Condair supplier.
– The connection material must be pressure-proof and certied for use in drinking water systems.
– Important! Before connecting the water line, the supply water line must be well ushed out.
CAUTION!
The thread at the humidier connection is made of plastic. To avoid overtightening, the union nut
of the water pipe must be tightened by hand only.
Water drain
The water drain is to be carried out according to the gure found in chapter chapter 5.5.1 and the appli-
cable local regulations for water installations. The indicated connection specications must be observed.
– Make sure that the drain pipe is correctly attached and easily accessible for inspections and cleaning
purposes.
– The draining temperature is: 80…90 °C (with optional drain water cooling <60°C). Use temperature-
resistant installation materials only!
– Lead drain line down to the funnel with a constant downslope (min. 15 %/8.5°).
Note: On units with two steam cylinders each drain line must be led into a separate funnel with trap.
– Attach drain line in such a way, that it cannot slip out of the funnel and that it cannot bottom out in
the funnel.
– The open end of the drain line must not touch the funnel (min. air gap 2 cm).
– We recommend to install the funnel with an lateral off-set of 20 cm to the unit, to prevent damage
to humidier due to rising steam.
Manual
View the manual for the Condair EL here, for free. This manual comes under the category humidifiers and has been rated by 1 people with an average of a 8.6. This manual is available in the following languages: English. Do you have a question about the Condair EL or do you need help? Ask your question here