Installation Instructions

OVERVIEW - Engineer’s Specification

The BOSCH HMB system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a high-
speed communication bus and have the capacity for 6 channels of combined audio and data
on a single pair of wires. The field wiring for the communication bus may be configured for
either Style 4 or Style 7 supervision. The system shall have the capacity for Fire Fighters
Phone communication. The system shall have a minimum capacity of 2048 monitor and
control points.
The Master Panel shall contain an integral microphone, dual channel digital message
repeater, (DMR) and digital tone generator, 120 VAC power supply, and battery charger. The
system shall be modular in design, and shall be expandable such that additional system
control points may be configured. The system shall include integral self-diagnostic routines
that shall continually monitor system status, and shall indicate the precise type of trouble
conditions should they occur in the system. A trouble condition within the system shall cause
a trouble indication to be transmitted to the FACP.
Distributed panels shall provide a minimum of 4 Class "B" (Style Y) speaker circuits,
expandable to eight total. Alternately, panel may be configured for 4 Class "A" (Style Z)
speaker circuits. Panel will provide up to 6 simultaneous audio channels, up to 16 Fire
Phone circuits. Amplifiers will contain their own power supplies, battery chargers and provide
auxiliary power for other components. Speaker circuits shall be supervised for short and open
circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.
System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of
an alarm signal and evacuation message to the appropriate area. Non-Alarm areas may
receive alert tones and messages as required or activated by the FACP.
The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.
To prevent unauthorized tampering, the voice evacuation system shall disable the
microphone if the microphone is keyed continuously for 3 minutes or more. Systems that do
not have this feature shall not be acceptable.
P/N B-5010 REV. C
130 Perinton Parkway, Fairport, NY 11450
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189

View the manual for the Bosch MB-PWR here, for free. This manual comes under the category detectors and has been rated by 1 people with an average of a 7.5. This manual is available in the following languages: English. Do you have a question about the Bosch MB-PWR or do you need help? Ask your question here

Need help?

Do you have a question about the Bosch and is the answer not in the manual?

  • Receive updates on solutions
  • Get answers to your question

Question and answer

Number of questions: 0

General
BrandBosch
ModelMB-PWR | MB-PWR
Productdetector
LanguageEnglish
FiletypeUser manual (PDF)
Features
Product typePower supply
Device type-
Brand compatibilityBosch
Quantity per pack1 pc(s)
Power
Input voltage120 V
Input current1 A
Input frequency60 Hz
show more

Can't find the answer to your question in the manual? You may find the answer to your question in the FAQs about the Bosch MB-PWR below.

Is the manual of the Bosch MB-PWR available in English?

Yes, the manual of the Bosch MB-PWR is available in English .

Is your question not listed? Ask your question here

No results